Supporting Documentation · Sep 6, 2022

220-22 Accurate Tank Testing Results 11.11.2021.pdf

Preserved file SHA-2565056886fd05fe4e8d5680992ce3ebb5d3bff888eb7fe920a26ae4a645180a7f4

Indexed text

Page 1

Accurate Tank Testing LLC www.oiltanktesting.com P.O.BOX 366 Franklin Lakes, N.J. 07417 tnktst@msn.com | Office (201) 848-8224 | Fax (201) 847-0718 140 Greenwood Ave, Midland Park, N.J. 07432 N.J.D.E.P. #US00006 Thursday November 11, 2021 T. Slack Environmental Services 4180 Market Street Kenilworth, NJ 07033 Re: 1-2,000 Galion, Diesel Stip3 Underground Storage Tank Cherry Lane Pump Station Cherry Lane West Orange, NJ 07052 Dear Sir/Madam, Enclosed please find the result of the EZY3 Locator Plus acoustic precision evaluation performed on the 2,000 gallon, diesel fuel oil underground storage tank and associated piping located at the above referenced property. All tank evaluations conform to U.S.E.P.A. and N.J.D.E.P. tank testing criteria and the results are as follows: DATE TANK RESULT (PASS/FAIL) 41/10/21 2,000 gallon diesel FAIL The tank contained 41.00" of fuel and 0.0" of water at the time of the test. The acoustical profile indicates a leak above or below the liquid level is the cause of the test failure. If this tank is to remain in service the tank must be investigated to determine the exact cause of the test failure. Examples of leaks are: corroded or loose - fill pipes, air vent pipes, compression fittings and/or corrosion holes in the tank itself. Possible options for investigating the cause of failure are: uncovering the tank top and inspecting all the piping and connections, isolating the tank from the piping and retesting the tank separately. If repairs are made, the tank must be retested to ensure integrity of the tank and associated piping for the tank to remain in service. Sometimes the expense to perform this work is costly and replacement of the tank may be warranted. If you choose to investigate the reason for the failure via isolation test, please contact us when the tank top is completely excavated so that a retest can be performed before the tank is backfilled. This allows us to thoroughly Investigate the tank system before the tank is put back in service. Accurate recommends isolating piping at sump and retesting tank. If you have any questions or require additional information, please do not hesitate to contact me. Thank you, Kevin Richards NJDEP #249447

Page 2

EZY 3 LOCATOR PLUS MANUFACTURED BY: ESTABROOK'S INC. 1-877-368-7215 VACUUM CALCULATION WATER SENSOR CALIBRATION DATE 44/11/21 Test Operator: Kevin Richards Signed 2h TANK MATERIAL SW-Steel Stip3 Operator's State Certification # 249447 TOTAL TANK VOL. 2,000 GALLONS TEST # 1 Site ID # 4 CUSTOMER: T. Slack Envoironmental Services PRODUCT VOL. 41.0000 INCHES SITE: Cherry Lane Pump Station ULLAGE VOL. 31.0000 INCHES Cherry Lane West Orange, NJ PRODUCT TYPE DIESEL Vacuum Sensor Calculation 41.0000 x 0.031 = 4.271 PSI (1) INCHES OF PRODUCT WEIGHT OF PRODUCT 0.000 x .036 = 0.000 PSI (2) INCHES OF WATER IN TANK Line 1 + Line 2 = Total Positive Head Pressure In Tank = 4.2740 PSI (3) 0.0 x .036 = 0.000 PSI (4) INCHES OF WATER OUTSIDE TANK Total Head Pressure Minus Outside Water Pressure = 1.2710 +/-PSI (5) Always add .5 PSI + 0.5000 PSI (6) NOTE: If Line 6 is Less Than .5 PSI Line 7 Shall be .6 PSI TEST PRESSURE = 1.77 +/-PSI (7) Test Setpoint Range: _ 49.10 to 59.10 Inches W.C. ACOUSTIC TEST TIME TIME PRESSURE TEST RESULT: Failed Blower Started: 8:30 0.00 Test Pressure Reached: 9:00 59.10 Depth of Groundwater Determined: Blower Turned Off: 9:00 59.10 By: Not Applicable Test Began: 9:00 §9.10 Where: Not Applicable Test Ended: 9:30 57.40 WATER INTRUSION TEST PERIOD WATER SENSOR CALIBRATION + CI Water sensor used? Yes /No[__NO. Grade Height TT Dia. . 36" 72.00" paced: Cal #1 Cal #2 Cal #3 i Average: Boitom to NOTE: Grade 108.0" (Calculation for Test Period: 0 + 3780= 0.00000 + .05 = _ominutes |Our! round Ave. Cal. Factor Time of Test ai" Began; ___ Water in \ Ended:

Page 3

Accurate Tank Testing LLC. VACUUM TREND ANALYSIS DATE: 14/41/2021 PBS# (NEW YORK): TOTAL TANK VOL.(Gal): TANK#: = = PRODUCT VOL {In}: LOCATION: ULLAGE VOL.(in): Cherry Lane Pump Station PRODUCT TYPE: _ “__CherryLane = West Orange, NJ 0 START MAX OFF TEST TIME DATA ne RPH WATER 3:00 59.4 9:05 58.7) 04 9:10 58.4) 0.3) 9:15 58.4 0.3) 9:20 57.8 0.3) 9:25 57.6 0.2) 9:30 57.4 0.2! THE ACOUSTIC CHARACTERISTIC OF A LEAK REVEALS: TIGHT TANK THIS UNDERGROUND STORAGE TANK PASSES THE CRITERIA SET FORTH BY THE US. EPA. ULLAGE (DRY) PORTION LEAK THIS UNDERGROUND STORAGE TANK FAILS THE CRITERIA SET FORTH BY THE U.S. EPA. BELOW PRODUCT LEVEL (WET) PORTION LEAK THIS UNDERGROUND STORAGE TANK FAILS THE CRITERIA SET FORTH BY THE US. EPA. WATER SENSOR INDICATES. (CHECK ONLY ONE) NO WATER INTRUSION WATER INTRUSION x NOT APPLICABLE SIGNATURE OF OPERATOR: Bertie PRINT NAME: Kevin Richards CERTIFICATION #: 08-5831 EXPIRATION DATE: 3/12/2023 Accurate Tank Testing LLC. P.O. Box 368 Franklin Lakes, NJ 07417 tnktst@msn.com Tel (201) 848-8224 Fax (204 847-0718

File revisions (1)