Show all pages7 27. Sheets SP-6 and SP-13 show San. MH #1-9 having 1 pipe entering the manhole and 2 pipes exiting the manhole which is incorrect. The plans must be revised to show that 2 pipes (6" & 8") are entering the manhole and one pipe (8") is leaving the manhole. In addition, the 6" pipe invert elevation cannot be lower than the invert elevation of the 8" pipe exiting the manhole. PETRY RESPONSE: The plans have been revised to correct the invert information. The 8” pipe inverts are correct, while the 6” pipe will be revised to enter the manhole at an invert of 421.39 (See Sheets SP-6 & SP-13). 28. Sheets SP-6 and SP-13 show San. MH #1-6 having 1 pipe entering the manhole and 2 pipes exiting the manhole which is incorrect. The plans must be revised to show that 2 pipes (6" & 8") are entering the manhole and one pipe (8") is leaving the manhole. In addition, the 6" pipe invert elevation cannot be lower than the invert elevation of the 8" pipe exiting the manhole. PETRY RESPONSE: The plans have been revised to correct the invert information. The 8” pipe inverts are correct, while the 6” pipe will be revised to enter the manhole at an invert of 414.51 (See Sheets SP-6 & SP-13). 29. The pipe slopes shown on Sheet SP-6 do not agree with the slopes shown on sheet SP-13 for the following pipe runs: a. San. MH #1-9 to San. MH #1-8 b. San. MH #1-8 to San. MH #1-7 c. San. MH #1-7 to San. MH #1-6 d. San. MH #1-6 to San. MH #1-5 PETRY RESPONSE: The pipe slopes on Sheet SP-13 are correct. The pipe slopes on Sheet SP-6 have been revised to match. 30. It shows on sheet SP-6 that the 8" sewer line from the grease trap to San. MH #1-7 will have a slope of 0.0% which is unacceptable. PETRY RESPONSE: This pipe slope has been revised to reflect the correct slope of 0.010 ft/ft. 31. Sheets SP-6 and SP-14 show both a 6" pipe and an 8" pipe exiting San. MH #2-7 which is incorrect. The plans must be revised to show that the 6" pipe is entering the manhole and the 8" pipe is leaving the manhole.
File revisions (1)
- Sep 29, 2026
59bc435674a0243,997 bytes