CME Associates Review 2

Preserved file SHA-2569f6c54fcaad1045ff088477275ded26c2c05aeb9398905d76c26c3ee1af68d76

Indexed text · page 7

Show all pages
Page 7

\ ASSOCIATES Chairman and Members of the West Orange Township Planning Board July 29, 2024 Re: West Essex Highlands, LLC (PB 24-01) Our File No, VWRP0179.01 Preliminary & Final Site Plan - Review #2 Page 7 19. 20. 21. 22. 23. 24. 25. 26. 27. 28. provided to the buildings as it appears a full height curb is proposed in front of the handicap parking space aisle. The grading plans must be revised to indicate the top of curb and grade elevations of all proposed full height curb and flush curb. Additionally, spot elevations must be added to all ADA ramps and ADA accessible landing areas. Additional spot elevations must be added to the handicap accessible parking spaces on the west side of the roadway across from Building D.1. Spot elevations must be added to the northern corner of Building B, the corners of the Clubhouse Building, the corners of the Pump Station Building, and the rear of Building D.1. Further, spot elevations must be added to southerly door at Building B, the northerly door at Building C, the easterly door with steps at Building C, the doors at the Clubhouse Building, the doors on each side of the Kennel Building, the door at the Maintenance Building, and the doors along the east side of Building D. It shows on sheets SP-13 and SP-14 that the dog kennel building has a finish floor elevation of 563 whereas the ground elevation in front of the door on the easterly side of the building is approximately 557.9 and the ground elevation in front of the door on the westerly side of the building is approximately 558.5. The grading must be adjusted to provide proper access to the building. Sheet SP-13 must be revised to label the contours between Building A.1 and Kuzik Drive. Additionally, the contours on the north and easterly side of Kuzik Drive across from Building A.1 and the Maintenance Building must be labeled. Sheets SP-13 and SP-14 shall be revised to clarify or remove the unlabeled contour that ties into the maintenance building between the proposed 560 and 562 contours and ties into the Kennel Building between the proposed 558 and 560 contours. Additionally, the spot elevation at the northeastern corner of the Kennel building shall be evaluated. Sheet SP-15 must be revised to include additional elevation information for the retaining walls east of the clubhouse. Sheets SP-16 and SP-17 shall be revised to label the proposed

Page 7

all be evaluated. Sheet SP-15 must be revised to include additional elevation information for the retaining walls east of the clubhouse. Sheets SP-16 and SP-17 shall be revised to label the proposed contours on the east and west sides of building D.2. Detail No. 10 on Sheet SP-59 must be named. The plans should be revised to include details of the following improvements that are proposed: a) Keep Right Around Circle sign. b) Electric Vehicle parking space sign. c) Pump stations. d) Emergency access drive to Howell Drive. S:\West Orange\Planning Board\VWRPO179.01 - West Essex Highlands, Inc\Review #2 07-29-24 docx

File revisions (1)