262 270 Main St 2026 05 26 Compliance 100 Planning Set

Preserved file SHA-2561ba611b9aaa2949e97947a37acd85a5eed1569abc3d31718296440e3d4d3c3cf

Indexed text · page 5

Show all pages
Page 5

PRINCIPAL IN CHARGE PROJECT TEAM CHECKED BY SHEET DESCRIPTION ISSUED FOR: SHEET NUMBER COPYRIGHT © JORGE MASTROPIETRO ATELIER ARCHITECTS JORGE E. MASTROPIETRO NY LICENSE NO. 036208-1 NJ LICENSE NO. 21AI02390400 ARCHITECT: OWNER: CONSULTANTS: DOB APPROVAL STAMP: ARCHITECT'S SEAL: PROJECT: 262-270 MAIN STREET WEST ORANGE ESSEX COUNTY, NJ 07052 BLOCK 114, LOT 50 & 55 262 MAIN STREET REALTY LLC 262-270 MAIN STREET WEST ORANGE, NJ 07052 646 427 9908 A0.01D GENERAL NOTES JM CC JM PROGRESS DATE: 05-26-2026 TRAFFIC ENGINEER DOLAN&DEAN CONSULTING ENGINEERS, LLC 181 WEST HIGH STREET SOMERVILLE, NJ 08876 908 927 0100 STRUCTURAL ENGINEER HUDSON ENGINEERING, LLC. 25 W8TH STREET, BSMT BAYONNE, NJ 07002 201 614 5304 CIVIL ENGINEER HUDSON ENGINEERING, LLC. 25 W8TH STREET, BSMT BAYONNE, NJ 07002 201 614 5304 CONSTRUCTION NOTES 1. GENERAL: ALL WORK TO BE COMPLETED IN ACCORDANCE WITH THE 2021 INTERNATIONAL BUILDING CODE - NJ EDITION, AND REGULATIONS OF ALL OTHER AGENCIES HAVING JURISDICTION. 2. MEANS OF EGRESS: ALL MEANS OF EGRESS SHALL BE MAINTAINED CLEAR AND FREE OF ALL OBSTRUCTIONS, SUCH AS BUILDING MATERIALS, TOOLS, ETC. 3. FIRE SAFETY: A. ALL BUILDING MATERIALS WHICH ARE STORED AT THE SITE OR ANY AREA OF THE BUILDING ARE TO BE STORED IN A LOCKED AREA. ACCESS TO THE AREA TO BE CONTROLLED BY THE GENERAL CONTRACTOR OR HIS REPRESENTATIVE. B. ALL MATERIALS TO BE STORED IN A ORDERLY FASHION. C. ALL FLAMMABLE MATERIALS TO BE KEPT TIGHTLY SEALED IN THEIR RESPECTIVE MANUFACTURERS' CONTAINERS. SUCH MATERIALS ARE TO BE KEPT AWAY FROM HEAT. D. ALL FLAMMABLE MATERIALS TO BE USED AND STORED IN AN ADEQUATELY VENTILATED SPACE. E. ALL ELECTRICAL POWER TO BE SHUT OFF WHERE THERE ARE EXPOSED CONDUITS. F. ALL ELECTRICAL POWER IN THE CONSTRUCTION AREA TO BE SHUT OFF AFTER WORKING HOURS. G. CONTRACTOR, AT ALL TIMES, IS TO ENSURE THERE IS NO NATURAL GAS LEAKAGE IN THE BUILDING, OR ANY FLAMMABLE GAS TO BE USED DURING CONSTRUCTION. 4. DUST CONTROL: DEBRIS, DIRT, AND DUST TO BE CLEANED UP AND CLEARED FROM THE BUILDING SITE DAILY TO AVOID EXCESSIVE ACCUMULATION. 5. PROTECTION A. CONTRACTOR TO PROVIDE ADJOINING PROPERTY PROTECTION IN ACCORDANCE WITH CODE REQUIREMENT (NJAC 5:23-2.15 (f)1.I(1) & 5:23-2.34). B. CONSTRUCTOR SHALL TAKE EVERY APPROPRIATE PRECAUTION IN ACCORDANCE WITH CURRENT BUILDING CODES AND CONSTRUCTION PRACTICES TO ENSURE ADJOINING PROPERTIES ARE PROTECTED FROM DAMAGE DURING

Page 5

5:23-2.34). B. CONSTRUCTOR SHALL TAKE EVERY APPROPRIATE PRECAUTION IN ACCORDANCE WITH CURRENT BUILDING CODES AND CONSTRUCTION PRACTICES TO ENSURE ADJOINING PROPERTIES ARE PROTECTED FROM DAMAGE DURING DEMOLITION AND CONSTRUCTION. C. BEFORE COMMENCE ANY WORK THE CONSTRUCTOR SHALL NOTIFY THE NEIGHBOURS ON BOTH SIDES PRIOR TO COMMENCEMENT OF ANY WORK. 1250 BROADWAY, 36TH FL, NEW YORK, NY 10001 PHONE 646.248.6664 WWW.JMAPC.COM G. DRYWALL 1. EXPOSED GYPSUM BOARD: ASTMC36 A. TYPE X WHERE INDICATED AND WHERE REQUIRED FOR FIRE-RESISTANCE RATING INDICATED. B. LONG EDGES: STANDARD TAPER C. THICKNESS: 5/8", OR AS SHOWN ON DRAWINGS. 2. TRIM ACCESSORIES A. PROVIDE MANUFACTURER'S STANDARD METAL TRIM ACCESSORIES, OF THE BEADED TYPE WITH FACE FLANGES FOR CONCEALMENT IN JOINT COMPOUND EXCEPT WHERE SEMI-FINISHING OR EXPOSED TYPE LOCATIONS. B. CORNER BEADS AT EXTERNAL CORNERS C. EDGE TRIM OF THE SHAPE INDICATED WHERE EDGE OF GYPSUM BOARD WOULD OTHERWISE BE EXPOSED OR SEMI- EXPOSED: L-TYPE FOR TIGHT ABUTMENT AT EDGES, OTHERWISE U-TYPE AS NEEDED/ REQUIRED. D. CONTROL JOINT UNITS, OF METAL AT LOCATIONS RECOMMENDED BY THE MANUFACTURER. 3. CONCEALED ACOUSTICAL SEALANT: NON-SHRINKING, NON- DRYING, NON-MIGRATING, NON- STAINING, MASTIC. 4. EXPOSED ACOUSTICAL SEALANT: LATEX, ACRYLIC, OR ACRYLIC-LATEX TYPE, PERMANENTLY ELASTIC AND PAINTABLE. 5. JOINT TAPE: ASTM C475, PERFORATED 6. JOINT COMPOUND: ASTM C 475, OF THE TYPE INDICATED. PROVIDE READY-MIXED VINYL-TYPE FOR INTERIOR WORK. PROVIDE 2 SEPARATE GRADES OF COMPOUND: ONE SPECIFICALLY FOR BEDDING TAPE AND ONE FOR TOPPING. 7. INSTALLATION SHALL BE PERFORMED ONLY BY AN APPLICATOR EXPERIENCED IN USING THIS PRODUCT AND SHALL USE TOOLS AND EQUIPMENT APPROVED BY THE MANUFACTURER. 8. INSTALL GYPSUM BOARDS IN LENGTHS AND DIRECTIONS WHICH WILL MINIMIZE NUMBER OF END JOINTS, AND AVOID END JOINTS IN CENTRAL AREA OF CEILINGS. 9. INSTALL WALLS AND PARTITIONS WITH EXPOSED GYPSUM BOARDS VERTICAL, WITH JOINTS OFFSET ON OPPOSITE SIDES OF PARTITIONS. OTHERWISE, INSTALL BOARDS AT RIGHT-ANGLES WITH SUPPORTS, EXCEPT WHERE RECOMMENDED IN A DIFFERENT ARRANGEMENT BY MANUFACTURER. 10. FORM CONTROL JOINTS WITH 1/2" SPACE BETWEEN BOARDS. INSTALL ACOUSTICAL SEALANT AT BASE OF SPACE, AND APPLY TRIM ACCESSORY AT FACE. 11. ACOUSTICAL SEALANT: DEMISING WALLS TO BE "SOUND RETARDING" WITH AN STC RATING OF 45 MIN.: APPLY 2 SEPARATE BEADS OF ACOUSTICAL SEALANT ALL AROUND

Page 5

T BASE OF SPACE, AND APPLY TRIM ACCESSORY AT FACE. 11. ACOUSTICAL SEALANT: DEMISING WALLS TO BE "SOUND RETARDING" WITH AN STC RATING OF 45 MIN.: APPLY 2 SEPARATE BEADS OF ACOUSTICAL SEALANT ALL AROUND AT INTERRUPTIONS OF DRYWALL WORK AS RECOMMENDED BY THE MANUFACTURER. 12. FORM "FLOATING" CONSTRUCTION FOR GYPSUM BOARDS AT INTERNAL CORNERS, EXCEPT WHERE SPECIAL ISOLATION OF EDGE TRIM IS INDICATED. 13. ISOLATE DRYWALL WORK FROM ABUTTING STRUCTURAL AND MASONRY WORK; PROVIDE EDGE TRIM AND ACOUSTICAL SEALANT AS RECOMMENDED BY THE MANUFACTURER. 14. INSTALL WATER-RESISTANT BACKING BOARDS WHERE SHOWN TO RECEIVE TILE AND SIMILAR RIGID APPLIED FINISHES. DO NOT APPLY TAPE AND COMPOUND AT JOINTS. SEAL CUT EDGE, JOINTS AND PENETRATIONS WITH WATER-RESISTANT SEALANT PRIOR TO INSTALLATION. 15. SCREW GYPSUM BOARD TO SUPPORTS, JOINTS, STUDS, ETC. 16. EXCEPT AS OTHERWISE INDICATED, APPLY JOINT TAPE AND JOINT COMPOUND AT JOINTS (BOTH DIRECTIONS) BETWEEN GYPSUM BOARDS. APPLY COMPOUND AT ACCESSORY FLANGES, PENETRATIONS, FASTENER HEADS, AND SURFACE DEFECTS. 17. INSTALL COMPOUND IN 2 COATS (PLUS PREFILL OF CRACKS WHERE RECOMMENDED BY MANUFACTURER); SAND AFTER LAST COAT. 18. APPLY SINGLE COAT USG IMPERIAL FINISH PLASTER, OR APPROVED EQUIVALENT, SMOOTH- TROWEL FINISH. 19. GENERAL STANDARD: GYPSUM ASSOCIATION SPECIFICATION GA-216, AND MANUFACTURER'S INSTRUCTIONS (WHICHEVER IS MORE STRINGENT). 20. MATERIALS (USG OR APPROVED EQUAL) H. GUARANTEES: 1. MATERIALS: THE CONTRACTOR SHALL FURNISH TO THE OWNER A 5 YEAR WRITTEN GUARANTEE ON ALL MATERIALS FURNISHED BY THOSE TRADES AS LISTED IN THIS SECTION TO BE FREE FROM DEFECTS DUE TO FAULTY WORKMANSHIP AND / OR MATERIALS. ALL DEFECTIVE MATERIAL SHALL BE REPLACED AS REQUIRED IMMEDIATELY AFTER PROPER NOTICE, AT NO COST TO THE OWNER. PART 7-THERMAL AND MOISTURE PROTECTION A. GENERAL 1. SEE GENERAL CONDITIONS 2. SEE PART IV - MASONRY B. MATERIALS 1. ASPHALTIC BITUMINOUS TROWEL ON DAMPPROOFING FOR FOUNDATIONS AND BELOW GRADE MASONRY WALLS. 2. CAULKING AND SEALANTS SHALL BE SELECTED BY THE CONTRACTOR TO SUIT CONDITIONS AND MATERIALS. A. CAULKING AND SEALANTS TO MATCH SURROUNDING SURFACE COLORS. B. ALL MATERIALS SHALL BE CAREFULLY SELECTED FOR COMPATIBILITY WITH EACH OTHER IN EACH JOINT SYSTEM. C. ALL MATERIALS SHALL BE INSTALLED AS PER THE MANUFACTURERS WRITTEN INSTRUCTIONS. 3. INSULATION SHALL BE INSTALLED IN THE TYPES AND SHAPES AS SHOWN ON THE

Page 5

BILITY WITH EACH OTHER IN EACH JOINT SYSTEM. C. ALL MATERIALS SHALL BE INSTALLED AS PER THE MANUFACTURERS WRITTEN INSTRUCTIONS. 3. INSULATION SHALL BE INSTALLED IN THE TYPES AND SHAPES AS SHOWN ON THE DRAWINGS AND AS FOLLOWS: A. FIBERGLASS ROLLS OR BATTS FACED WITH ALUMINUM FOIL VAPOR RESISTANT MEMBRANE WITH INTEGRAL NAILING FLANGES. I. EXTERIOR WALLS: 3 1/2", R-13 MIN. WHERE SHOWN OR NOTED ONLY. II. PROVIDE UNFACED BATTS AT INTERIOR PARTITION WALLS AND CEILINGS IN THE SIZES AS SHOWN ON THE DRAWINGS WHERE SHOWN OR REQUIRED FOR SOUND ABSORPTION REQUIREMENTS. III. ROOFS AND CEILINGS UNDER UNHEATED SPACES: 9", R-30 B. RIGID INSULATION SHALL BE INSTALLED IN THE SIZES AS SHOWN ON THE DRAWINGS, SHALL BE EXTRUDED AND HAVE AN "R" VALUE OF 5 PER INCH. I. INSULATION SHALL BE "STYROFOAM" BRAND AS MANUFACTURED BY THE DOW CHEMICAL CO. OR EQUAL. 4. PROVIDE A TOTAL ROOF DRAINAGE SYSTEM AS SHOWN OR REQUIRED, INCLUDING, BUT NOT LIMITED TO GUTTERS, LEADERS, CHIPS, CLEATS, CAPS, ROOF DRAINS, ETC. A. PREFINISHED COLOR AS SELECTED, ALL MATERIALS SHALL MATCH. B. 0.04" ALUMINUM GUTTER, PROFILE AND SIZES AS SHOWN ON DRAWINGS. (EXPANSION JOINTS AS REQUIRED TO PREVENT BUCKLING) C. 0.04" ALUMINUM DOWNSPOUT, PROFILE AND SIZES AS REQUIRED, TIE TO UNDERGROUND DRAINAGE SYSTEM. D. ALUMINUM HANGERS FOR GUTTER AND STRAPS FOR DOWN SPOUTS, SIZES AS REQUIRED FOR JOB APPLICATION. E. ALL ACCESSORIES, MITERS, SLIP JOINTS, CONNECTIONS, END CAPS, ELBOWS, EXPANSION JOINTS, ETC. F. 0.20" FLASHING AND COUNTER FLASHING. G. SEALING OF ALL JOINTS AS PER MANUFACTURER'S RECOMMENDATIONS. 5. FLASHINGS SHALL BE INSTALLED WHERE NOTED OR REQUIRED. A. ALL FLASHINGS AND ACCESSORIES SHALL BE OF CORROSIVE RESISTANT MATERIALS. B. ALL MATERIALS SHALL BE FULLY COMPATIBLE WITH ONE ANOTHER AND ADJOINING MATERIALS. C. DISSIMILAR MATERIALS - ALUMINUM SHALL NOT BE CONCRETE, STUCCO MASONRY OR CORROSIVE NONMETALLIC MATERIALS WHICH MIGHT BECOME REPEATEDLY WET. WOOD TREATED WITH SOME CHEMICALS CAN CAUSE PROBLEMS WHEN WET, SO USE ONLY TREATMENTS SUCH AS CREOSOTE, ZINC NAPHTHANATE PENTACHOLOROPHENAL (5% CONCENTRATION) OR WOLMAN SALTS. DO NOT PERMIT WATER FROM COPPER FLASHING TO DRAIN OVER ALUMINUM PRODUCTS. 6. ROOFING SHALL BE INSTALLED IN THE LOCATIONS AS SHOWN ON THE DRAWINGS AND SHALL BE AS FOLLOWS: I. MODIFIED BITUMEN ROOF SEE MANUFACTURER'S RECOMMENDATIONS II. 15# ASPHALT SATURATED FELT UNDERLAYMENT. III. ALL ROOFING

Page 5

E INSTALLED IN THE LOCATIONS AS SHOWN ON THE DRAWINGS AND SHALL BE AS FOLLOWS: I. MODIFIED BITUMEN ROOF SEE MANUFACTURER'S RECOMMENDATIONS II. 15# ASPHALT SATURATED FELT UNDERLAYMENT. III. ALL ROOFING MATERIALS SHALL BE MANUFACTURED AND SUPPLIED BY A SINGLE ROOFING MANUFACTURER: CERTAINTEED, GEORGIA-PACIFIC OR APPROVED EQUAL. VII. COLOR BY ARCHITECT / OWNER. C. SOLID WOOD SIDING HORIZONTAL SIDING PANELS SHALL HAVE 4" NOMINAL EXPOSURE WITH DOUBLE BEVEL. 1. SIDING TO HAVE FINISH AS SPECIFIED BY ARCHITECT/OWNER 2. WORKMANSHIP AND INSTALLATION I. BEFORE STARTING WORK, VERIFY GOVERNING DIMENSIONS OF BUILDING EXAMINE, CLEAN, REPAIR IF NECESSARY, ANY ADJOINING WORK ON WHICH THIS WORK IS IN ANY WAY DEPENDENT FOR ITSPROPER INSTALLATION. II. ALL WORK SHALL BE INSTALLED IN A COMPLETE PROFESSIONAL, WORKMANLIKE FASHION BY THOSE SKILLED IN THEIR TRADES AND IN STRICT ACCORDANCE WITH MANUFACTURERS WRITTEN INSTRUCTIONS. III. COMPLY WITH ALL APPLICABLE CODES, ORDINANCES, AND SAFE WORK PRACTICES. IV. ALL WORK EXPOSED TO VIEW SHALL BE INSTALLED TRUE TO LINE, AT PROPER ELEVATIONS, AND IN ALIGNMENT WITH OTHER WORK. V. INSTALL WOOD SIDING IN ACCORDANCE APPLICABLE CODES VI. UPON COMPLETION OF THIS WORK, ALL SIDING, ETC. SHALL BE CLEANED SO THAT NO SOILED AREAS, FINGERPRINTS, ETC. ARE VISIBLE TO THE NAKED EYE. ALL SCRAP SHALL BE REMOVED AND PROPERLY DISCARDED. D. GUARANTEES 1. MATERIALS: THE CONTRACTOR SHALL FURNISH TO THE OWNER A 15 YEAR WRITTEN GUARANTEE ON ALL MATERIALS FURNISHED BY THOSE TRADES AS LISTED IN THIS SECTION TO BE FREE FROM DEFECTS DUE TO FAULTY WORKMANSHIP AND / OR MATERIALS. ALL DEFECTIVE MATERIAL SHALL BE REPLACED AS REQUIRED IMMEDIATELY AFTER PROPER NOTICE, AT NO COST TO THE OWNER. 2. THE CONTRACTOR SHALL GUARANTEE ALL ROOFING, WATERPROOFING, FLASHINGS, ETC. TO BE FREE FROM LEAKS FOR A PERIOD OF NOT LESS THAN 20 YEARS FROM DATE OF FINAL ACCEPTANCE. PART 8 - OPENINGS (SEE WINDOW / DOOR SCHEDULES) PART 9 - FINISHES (WHERE APPLICABLE) A. GENERAL 1. SEE GENERAL CONDITIONS 2. THE CONTRACTOR SHALL PROVIDE ALL ITEMS, MATERIALS ETC. AS SHOWN OR NOTED ON THE DRAWINGS OR DESCRIBED HEREIN, INCLUDING LABOR, EQUIPMENT ANY OTHER ITEMS REQUIRED FOR THE COMPLETE INSTALLATION OF ALL FINISHES. A. THE OWNER SHALL BE RESPONSIBLE FOR FINAL SELECTION OF ALL FINISH MATERIALS AND COLORS. B. MATERIALS 1. RESILIENT FLOOR COVERINGS SHALL BE INSTALLED IN THE LOCATIONS AS SHOWN AND NOTED

Page 5

ALL FINISHES. A. THE OWNER SHALL BE RESPONSIBLE FOR FINAL SELECTION OF ALL FINISH MATERIALS AND COLORS. B. MATERIALS 1. RESILIENT FLOOR COVERINGS SHALL BE INSTALLED IN THE LOCATIONS AS SHOWN AND NOTED ON THE DRAWINGS. A. RESILIENT FLOORING CONTRACTOR SHALL INSPECT ALL SUBFLOORING AND IMMEDIATELY REPORT FINDINGS TO THE OWNER. B. ALL FLOOR COVERINGS SHALL CONFORM TO ALL APPLICABLE FEDERAL SPECIFICATIONS. C. ALL MATERIALS SHALL BE NEW AND FREE FROM DEFECTS; BEST COMMERCIAL GRADE FOR EACH SPECIFIC FUNCTION AND SITUATION. D. ALL PRIMERS AND ADHESIVES SHALL BE COMPATIBLE WITH FLOOR FINISH AS RECOMMENDED BY THE MANUFACTURER. E. VINYL BASES SHALL BE THE COVE TYPE AND SHALL BE .085" X 4" MOLDED VINYL. 2. CERAMIC TILE (WHERE/ IF APPLICABLE ) A. INSTALL CERAMIC TILE WHERE SHOWN ON THE PLANS AND IN ACCORDANCE WITH ALL MANUFACTURES REQUIREMENTS AND ANSI STANDARDS. B. COLORS AND PATTERNS BY ARCHITECT/ OWNER. C. CERAMIC TILES SHALL BE IN THE SHAPES AND SIZES AS SPECIFIED IN ELEVATIONS I. FURNISH COMBINATION COVE AND BASE COMPLETE WITH COMBINATION ANGLES AND STRETCHER SHAPES FOR INTERNAL AND EXTERNAL CORNERS AND ANY OTHER SHAPES AND ACCESSORIES AS REQUIRED FOR THE COMPLETE INSTALLATION OF CERAMIC TILE. 3. PAINTING ALL SURFACES TO BE PAINTED SHALL BE CLEAN, PROPERLY PREPARED IN ACCORDANCE WITH PAINT MANUFACTURES PRINTED INSTRUCTIONS. PROTECT ADJACENT SURFACES AS NECESSARY. CLEAN ALL DRIPS AND SPATTERS. COLOR AND GLOSS OF INTERIOR SPACES SHALL BE SELECTED BY THE OWNER. EXTERIOR PAINT COLORS SELECTED BY OWNER AND APPROVED BY ARCHITECT. THE PAINTING AND FINISHING OF ALL INTERIOR AND EXTERIOR ITEMS AND SURFACES SHALL BE AS FOLLOWS: A. EXTERIOR WOOD AND TRIM SHALL RECEIVE 1 COAT OF PRIMER AND 2 FINISH COATS OF ALKYD OIL ENAMEL. B. EXTERIOR AND INTERIOR FERROUS METAL SHALL BE PROPERLY PRIMED AND GIVEN 2 COATS OF ALKYD ENAMEL. C. INTERIOR GYPSUM DRYWALL SHALL BE PROPERLY PRIMED AND GIVEN 1 COAT LATEX - SEE FINISH SCHEDULE. D. INTERIOR WOOD WORK, DOORS AND TRIM SHALL BE GIVEN 1 COAT SEMI-TRANSPARENT ALKYD- OIL STAIN AND 1 COAT POLYURETHANE BOTH SIDES, TOP AND BOTTOM. E. INTERIOR EXPOSED CONCRETE FLOORS SHALL BE GIVEN 1 COAT OF CLEAR CONCRETE SEALER-DUST PROOFING. F. EXTERIOR STUCCO AND MASONRY SHALL BE GIVEN 2 COATS OF OIL BASED ENAMEL. G. PAINTS SHALL BE MANUFACTURED BY ONE OF THE FOLLOWING: BENJAMIN MOORE PAINTS CON- LUX PAINT CO. OR EQUAL C. INSTALLATION 1. ALL MATERIALS IN THIS

Page 5

MASONRY SHALL BE GIVEN 2 COATS OF OIL BASED ENAMEL. G. PAINTS SHALL BE MANUFACTURED BY ONE OF THE FOLLOWING: BENJAMIN MOORE PAINTS CON- LUX PAINT CO. OR EQUAL C. INSTALLATION 1. ALL MATERIALS IN THIS SECTION SHALL BE INSTALLED IN THE MOST PROFESSIONAL AND WORKMANLIKE MANNER, IN STRICT ACCORDANCE WITH THE MANUFACTURERS WRITTEN INSTRUCTION AND ALL APPLICABLE CODES AND STANDARDS. 2. INSTALL ALL ACCESSORIES, TRIM PIECES, ETC. AS REQUIRED FOR THE COMPLETE INSTALLATION OF EACH FINISH MATERIAL. 3. ALL MATERIALS SHALL BE ACCURATELY SCRIBED TO FIT PIPES, COLUMNS, AND ALL OTHER FEATURES AND SHALL BE NEATLY CUT AND BUTTED TO ALL WALLS BASES, ETC. 4. CERAMIC TILES SHALL BE SET PLUMB LEVEL AND TRUE TO LINE, ALL JOINTS SHALL BE UNIFORM; 1/4" RUN THRU FROM FLOORS TO WALL AND FROM WALL TO WALL. A. ALL TILE SHALL BE SET IN ACCORDANCE WITH THE TILE COUNCIL OF AMERICA STANDARDS AND WITH AN EPOXY ADHESIVE EXCEPT AT EXTERIOR AND WET APPLICATIONS WHERE TILE SHALL BE DRY SET MORTAR. B. GROUT SHALL BE PORTLAND CEMENT COMMERCIAL GRADE, COLOR SHALL BE WHITE AT ALL FLOORS AND WALLS. 5. PAINTING SHALL BE DONE BY THOSE SKILLED IN THEIR TRADE. APPLY ALL MATERIAL EVENLY. NO SAGS, RUNS, CRAWLS, OR OTHER DEFECTS SHALL BE ALLOWED. A. ALL SURFACES TO BE PAINTED SHALL BE THOROUGHLY AND UNIFORMLY COVERED, APPLY NECESSARY COATS TO COMPLETE JOB. D. PROTECTION AND CLEANING 1. ALL WORK SHALL BE PROTECTED BY A TEAR RESISTANT HEAVY WEIGHT KRAFT PAPER, TAPE ALL SEAMS. PAPER SHALL BE INSTALLED IN AREAS SUBJECT TO TRAFFIC WHICH WOULD BE DETRIMENTAL TO THE FINISHED SURFACE. ALL COVERINGS SHALL REMAIN IN PLACE FOR THE DURATION UNTIL THE BUILDING IS READY FOR OCCUPANCY. 2. EACH TRADE SHALL THOROUGHLY CLEAN AND MAKE GOOD ALL WORK IN THEIR CONTRACT. REMOVE ALL TRACES OF GROUT, DIRT, GREASE, ETC. TO THE SATISFACTION OF THE OWNER. E. GUARANTEES 1. MANUFACTURERS AND CONTRACTORS SHALL GUARANTEE ALL WORK FOR A PERIOD OF 2 YEARS FROM DATE OF FINAL ACCEPTANCE. ALL WORKMANSHIP AND MATERIALS SHALL BE FREE FROM DEFECTS. ALL REPAIRS SHALL BE PROMPTLY MADE. 2. CONTRACTORS SHALL PROVIDE OWNER WITH SURPLUS STOCK OF ALL FINISH PRODUCTS. 3. IN THE EVENT ANY ADJACENT AREAS DAMAGED AS THE RESULT OF THE FAILED PRODUCT THE DAMAGED WORK SHALL BE REPAIRED AT NO COST TO THE OWNER. INCLUDED ALSO SHALL BE ADJACENT AREAS WHICH MUST BE DISTURBED IN ORDER TO REPAIR DEFECTIVE MATERIALS. PART 10 - SPECIALTIES (NOT USED) PART 11 -

Page 5

DAMAGED WORK SHALL BE REPAIRED AT NO COST TO THE OWNER. INCLUDED ALSO SHALL BE ADJACENT AREAS WHICH MUST BE DISTURBED IN ORDER TO REPAIR DEFECTIVE MATERIALS. PART 10 - SPECIALTIES (NOT USED) PART 11 - SUPPLEMENTARY GENERAL CONDITIONS FOR MECHANICAL AND ELECTRICAL TRADES A. GENERAL CONDITIONS: ALL GENERAL CONDITIONS AS SET FORTH PREVIOUSLY ARE HEREBY MADE A PART OF THIS SPECIFICATION. B. MATERIALS AND WORKMANSHIP: ALL WORK SHALL BE PERFORMED BY COMPETENT MECHANICS, ACCORDING TO MANUFACTURERS' RECOMMENDATIONS AND IN ACCORDANCE WITH ACCEPTED GOOD PRACTICE OF THE VARIOUS TRADES. ALL MATERIAL SHALL BE AS SPECIFIED OR PERFECT CONDITION. WHERE PARTICULAR ITEMS OF MATERIAL ARE SPECIFIED, CONTRACTORS SHALL SUPPLY THE BEST QUALITY ITEMS. C. SLEEVES: CONTRACTOR FOR EACH TRADE SHALL FURNISH ALL GALVANIZED STEEL PIPE SLEEVES AS REQUIRED BY HIS WORK. D. CUTTING AND PATCHING: CONTRACTOR FOR EACH TRADE SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING AS REQUIRED BY HIS WORK. E. MEASUREMENTS TO BE VERIFIED: BEFORE ORDERING ANY MATERIALS OR COMMENCING WITH ANY WORK, THE CONTRACTORS SHALL VERIFY ALL MEASUREMENTS AND CONDITIONS AT THE SITE AND SHALL ASCERTAIN THE CORRECTNESS OF SAME. NO EXTRA CHANGE OR COMPENSATION WILL BE ALLOWED ON ACCOUNT OF DIFFERENCES BETWEEN ACTUAL DIMENSIONS / JOB CONDITIONS AND THOSE INDICATED ON THE DRAWINGS. F. EXAMINATION OF DOCUMENTS, BUILDING AND SITE: THE BIDDERS ARE REQUIRED TO EXAMINE THE BUILDING AND SITE OF THE WORK AND TO EXAMINE AND BECOME FAMILIAR WITH PLANS, SPECIFICATIONS AND ALL OTHER CONTRACT DOCUMENTS PERTAINING TO THE PROPOSED WORK. SUBMISSION OF A BID SHALL BE SUFFICIENT TO ESTABLISH THE PRESUMPTION THAT THE BIDDER HAS INVESTIGATED THE SITE OF WORK AND IS SATISFIED AS TO ALL CONDITIONS ENCOUNTERED, THE CHARACTER, QUALITY AND QUANTITY OF THE WORK TO BE PERFORMED, AND THE MATERIALS FURNISHED IN COMPLETION THEREOF. G. TEMPORARY LINES: CONTRACTORS SHALL MAINTAIN CONTINUITY OF ALL SERVICES WITHIN THE BUILDING OR SITE DURING THE COURSE OF CONSTRUCTION, PROVIDING TEMPORARY LINES AS REQUIRED. H. SUPPORTS: SUPPORTS FOR ALL MECHANICAL AND ELECTRICAL EQUIPMENT REQUIRING SAME SHALL BE FURNISHED BY RESPECTIVE CONTRACTORS. ALL EQUIPMENT HUNG FROM OVERHEAD CONSTRUCTION SHALL HAVE WEIGHT OF EQUIPMENT DISTRIBUTED BY USE OF ANGLE OR CHANNELED FROM SUPPORTS AS NECESSARY AND APPROVED, WITH SAME SUBSTANTIALLY FASTENED TO STRUCTURAL SUPPORT SYSTEM. ANY

Page 5

VERHEAD CONSTRUCTION SHALL HAVE WEIGHT OF EQUIPMENT DISTRIBUTED BY USE OF ANGLE OR CHANNELED FROM SUPPORTS AS NECESSARY AND APPROVED, WITH SAME SUBSTANTIALLY FASTENED TO STRUCTURAL SUPPORT SYSTEM. ANY WALL-MOUNTED EQUIPMENT WHICH CANNOT BE SUPPORTED FROM ARCHITECTURAL OR STRUCTURAL MATERIALS, SHALL HAVE ITS OWN INDEPENDENT SUPPORT SYSTEM FURNISHED BY THE CONTRACTOR. PROPER INSTALLATION METHOD SHALL BE AS APPROVED BY ARCHITECT. I. DAMAGED WORK: EACH CONTRACTOR SHALL PROTECT AND LEAVE IN PERFECT CONDITION ALL MATERIALS, APPARATUS FITTINGS, FIXTURES AND TRIM IN THE SCOPE OF HIS CONTRACT. SHOULD ANY ITEMS BE DAMAGED OR BROKEN, OR WORKMANSHIP MOLESTED, NO MATTER BY WHOM SUCH DAMAGE IS CAUSED, THE WORK MUST BE CORRECTED AND DAMAGED ITEMS REPLACED WITH NEW ITEMS, BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER. ANY WORK WHICH NEEDS REDOING BECAUSE CONTRACTORS RELATIVE TO DAMAGE SHALL BE DONE BY THE SKILLED TRADE WHICH ORIGINALLY PERFORMED SUCH WORK. ANY ADJUSTMENTS BETWEEN CONTRACTORS RELATIVE TO DAMAGE TO WORK OR MATERIALS, SHALL NOT BE THE RESPONSIBILITY OF THE OWNER, ARCHITECT, ENGINEER OR THEIR REPRESENTATIVES. J. CHARTS AND TAGS: ALL VALVES, DAMPERS, CONTROLS SHALL BE DESIGNED BY DISTINGUISHING NUMBERS AND/OR LETTERS ON REQUIRED CHARTS AND/OR DIAGRAMS. THE CONTRACTOR SHALL INSTALL APPROVED TAGS FOR ALL DESIGNATED ITEMS, WITH NUMBERS AND/OR LETTERS ON THE TAGS CORRESPONDING TO THOSE ON THE CHARTS AND/OR DIAGRAMS. K. MANUFACTURER'S INSTRUCTIONS: PROVIDE FOR EACH ITEM OF EQUIPMENT OR APPARATUS FURNISHED A COMPLETE SET OF PRINTED INSTRUCTIONS OBTAINED FROM THE MANUFACTURER COVERING OPERATION, CARE, LUBRICATION, CLEANING SERVICING, ADJUSTING, ETC., OF ITEMS INVOLVED TOGETHER WITH SPECIAL SAFETY INSTRUCTIONS, PARTICULARLY INSTRUCT OWNER'S REPRESENTATIVE WHO WILL OPERATE PLANT IN ALL SUCH DETAILS. L. MANUFACTURER'S DIRECTIONS: THESE SHALL BE FOLLOWED IN ALL CASES WHERE MANUFACTURER FURNISHES DIRECTIONS COVERING POINTS NOT SHOWN IN DRAWINGS AND SPECIFICATIONS. M. OPERATING, MAINTENANCE AND INSTRUCTION DATA: SUBMITTED TO THE OWNER FOR APPROVAL PRIOR TO ACCEPTANCE OF INSTALLATION, COMPLETE AND AT ONE TIME. N. GUARANTEES: ALL WORK COMPLETED GUARANTEED FOR A MINIMUM OF ONE YEAR EXCEPT FOR EXTENDED PERIOD FOR COMPRESSORS, ETC. NJ IBC 2021 - SPECIAL INSPECTIONS INSPECTION CODE STEEL CONSTRUCTION IBC 1705.2 STRUCTURAL STEEL IBC 1705.2.1 COLD FORMED STEEL DECK IBC

Page 5

UM OF ONE YEAR EXCEPT FOR EXTENDED PERIOD FOR COMPRESSORS, ETC. NJ IBC 2021 - SPECIAL INSPECTIONS INSPECTION CODE STEEL CONSTRUCTION IBC 1705.2 STRUCTURAL STEEL IBC 1705.2.1 COLD FORMED STEEL DECK IBC 1705.2.2 OPEN WEB STEEL JOIST GRIDERS IBC 1705.2.3 COLD FORMED STEEL TRUSSES SPANING 60' OR GREATER IBC 1705.2.4 CONCRETE CONSTRUCTION IBC 1705.3 WELDING OF REINFORCING BARS IBC 1705.3.1 MATERIAL TESTS IBC 1705.3.2 MASONRY CONSTRUCTION IBC 1705.4 GLASS UNIT MASONRY AND MASONRY VENEER IN RISK CATEGORY IV IBC 1705.4.1 VERTICAL MASONRY FOUNDATION ELEMENTS IBC 1705.4.2 SOILS IBC 1705.6 DRIVEN DEEP FOUNDATIONS IBC 1705.7 CAST-IN-PLACE DEEP FOUNDATIONS IBC 1705.8 HELICAL PILE FOUNDATIONS IBC 1705.9 STRUCTURAL INTEGRITY OF DEEP FOUNDATION ELEMENTS IBC 1705.10 FABRICATED ITEMS IBC 1705.11 SPECIAL INSPECTIONS FOR SEISMIC RESISTANCE IBC 1705.13 TESTING FOR SEISMIC RESISTANCE IBC 1705.14 SPRAYED FIRE-RESISTANT MATERIALS IBC 1705.15 MASTIC AND INTUMESCENT FIR-RESISTANT COATINGS IBC 1705.16 EXTERIOR INSULATION AND FINISH SYSTEM IBC 1705.17 WATER RESISTIVE BARRIER COATING IBC 1705.17.1 FIRE-RESISTANT PENETRATION & JOINTS IBC 1705.18 PENETRATION FIRESTOPS IBC 1705.18.1 FIRE-RESISTANT JOINT SYSTEM IBC 1705.18.2 TESTING FOR SMOKE CONTROL IBC 1705.19 SEALING OF MASS TIMBER IBC 1705.20 No. Date Description