E. LIGHTING COMMENTS 1. In accordance with Section 25-14.1b of the Township Code, the Lighting & Landscape Plan (sheet 7) should be revised to indicate all lighting fixtures will be directed downward and equipped with shielding so as to prevent the direct source of light from being visible from any point beyond the property lines of the premises upon which the light is located. This comment has been addressed, and the lighting notes have been revised to indicate all lighting fixtures will be directed downward and equipped with shielding. In accordance with Section 25-14.3 of the Township Code, the Lighting & Landscape Plan (sheet 7) should be revised to provide a minimum illumination of 0.6 fc within pedestrian walkways and a minimum illumination of 1.5 fc within the parking area. This comment has been addressed, and sheet #7 has been revised to provide a minimum illumination of 0.6 fc within pedestrian walkways and a minimum illumination of 1.5 fe within the parking area Revise the Lighting & Landscape Plan (sheet 7) to indicate proposed lighting timers and hours of operation. This comment has been addressed, and sheet #7 has been revised to indicate proposed lighting timers and hours of operation. Revise the ‘Area light Foundation Detail’ on the Lighting & Landscape Plan (sheet 7) to indicate a concrete strength of 4,500 PSI. This comment has been addressed, and the ‘Area light Foundation Detail’ on sheet #7 has been revised to indicate a concrete strength of 4,500 psi. . Revise the plans to provide the catalog cuts for all proposed light poles and fixtures, for further review. Also, include ordering information for the proposed light pole. This comment has been addressed, and the catalog cuts and ordering information for all proposed light poles and fixtures have been provided. Revise the plans to indicate proposed color and finish for all fixtures and poles. This comment has been addressed, and #2 under the Lighting Notes indicates that all fixtures and poles are to be black.

File revisions (1)