Supporting Documentation · Jul 16, 2026
Acoustical Analysis 062826 resubmission 4901 2414 2009 v1
49e584bf5fb8b33db6b581ca9d9b0b19400be775c6874c35caa267a58e035087Indexed text
VIA EMAIL ONLY jmicik@mavis.com 28 June 2026 Mr. James Micik Mavis Tire Supply, LLC 100 Hillside Avenue White Plains, NY 10603 Re: Acoustical Analysis of Site Sound Emissions Proposed Mavis Tire Center #2296 460 Prospect Avenue, Township of West Orange, Essex County, NJ OAA File 5042A Dear Mr. Micik: As requested, Ostergaard Acoustical Associates (OAA) has carried out acoustical analyses to evaluate the potential site sound emissions of major noise sources associated with a proposed Mavis Tire Center located in West Orange, New Jersey. Site sound emissions must comply with applicable noise regulations. This study is based on the drawing Site Plan prepared by Dynamic Engineering, last revised on 25 June 2026. The project site is located on the eastern side of Prospect Avenue, just northeast of the intersection of Rooney Circle and Prospect Avenue. The property currently accommodates a two-story commercial building to be demolished. The site is located in the B-2, General Business, zoning district. An urgent care center and an event venue also in the B-2 district are located directly north and south of the site, respectively. West of the site across Prospect Avenue are various commercial retailers in the P-C, Planned Commercial, district as well as an electrical utility station in the O-R, Office Research, district. Of most acoustical interest are the residences abutting the site to the east in the PURD, Planned Unit Residential Development, district. The nearest of these residences is located about 70 feet from the closest service bay. The proposed plan calls for an approximately 6,200 ft2 retail facility, utilizing seven garage doors to provide access to vehicle service bays. The site is accessible via a primary driveway connecting to Prospect Avenue; there is also a shared driveway (Blueberry Bend) along the southern portion of the site. In coordination between OAA and Mavis, plans have been updated to call for an additional 6-foot-tall solid privacy fence, connecting the southeast corner of the building with the masonry trash enclosure, to provide additional noise mitigation in the direction of residential receptors to the east. The tire center will contribute steady and intermittent sound to off-site receptors. The primary noise source of interest is the interior sound emitted from servicing
Acoustical Analysis of Site Sound Emissions Proposed Mavis Tire Center #2296 - West Orange, NJ 28 June 2026 Page 2 vehicles, such as an impact wrench. Steady sound is produced by rooftop HVAC equipment. Patron activity sound is generally not considered the responsibility of the property owner. Local and State noise codes regulate site sound emissions. West Orange Township discusses noise in §4-4: Noise. This code section is qualitative in nature, generally prohibiting excessively loud and disturbing noise; no quantitative limits are given. The State of New Jersey Noise Control Regulation, found at N.J.A.C. 7:29, generally requires that steady sound from commercial or industrial properties contributes no more than 65 dB(A) at or within the property line of any residential or commercial receptor. During the nighttime hours (2200-to-0700 hours), the limit drops to 50 dB(A) at residential receptors, while the limit for commercial receptors remains 65 dB(A). There are no limits for industrial receptors. Note the daytime code limit is designed to protect speech communication, whereas the nighttime code limit is designed to mitigate sleep disturbances. The State regulation also provides limits in octave frequency bands that correspond to the 65 dB(A) and 50 dB(A) limits. The frequency bands cover the audible spectrum, from low- pitched sounds to high-pitched sounds; the limits are more permissive at lower frequencies because human hearing is less sensitive at low frequencies. In addition, impulsive noise, which is any noise less than one second in duration, is limited to 80 dB(A) measured using a sound level meter’s fast response, regardless of receptor type or time of day. It should be noted that regulatory limits apply at or within the nearest receptor property line. No limit applies at vacant properties or intervening right-of-way corridors that accommodate railroads, rivers, or roads. As stated above, regulatory limits apply at or within the property line of the receptor. Enforcement guidelines issued by the State* provide further direction indicating that compliance measurements should be made at the location of the affected person. This is defined as a location where recreation, repose, and conversation may reasonably occur. In other words, it is most appropriate to evaluate site sound where a complaint may reasonably occur, such as at upper-story
a location where recreation, repose, and conversation may reasonably occur. In other words, it is most appropriate to evaluate site sound where a complaint may reasonably occur, such as at upper-story window elevations or at locations 5 feet above grade within landscaped and/or hardscaped residential property areas (e.g. lawns, decks, pools, patios, etc.). No limits apply at intervening roads or rights- of-way. Exceedance of code limits without a formal complaint does not automatically result in a noise code violation. Professional experience is often relied upon to determine the likelihood of a noise complaint. In summary, Township noise ordinances call for minimization of noise disturbances. Meeting State noise limits accomplish this. Therefore, OAA used State noise code limits as project noise goals. * Guidelines for the Investigation of Noise Complaints Pursuant to the State of New Jersey Noise Control Regulation (N.J.A.C. 7:29) and the Model Noise Control Ordinance, 14 January 2025.
Acoustical Analysis of Site Sound Emissions Proposed Mavis Tire Center #2296 - West Orange, NJ 28 June 2026 Page 3 As the proposed tire center is anticipated to be operational only during daytime hours, operational sound should not exceed 65 dB(A) at nearby receptors. Because HVAC equipment will operate during the nighttime hours, it should meet the more stringent nighttime noise code limit of 50 dB(A) at residential receptors. While OAA acknowledges that commercial noise limits apply, the focus of this analysis was on the residential receptors as these receptors are closer and are more likely to be sensitive than commercial uses. Impact wrenches are the primary noise source associated with vehicle servicing. Based on OAA survey data at another Mavis Tire facility, impact wrench activity with the garage doors open produces maximum sound levels of 73 dB(A) at a distance of 50 feet. Impact wrench noise is primarily high-frequency sound. Given the proposed 6-foot solid fence will attenuate about 10 dB at higher frequencies, results indicate that such activity will be below the daytime noise code limit of 65 dB(A) at residential receptor vantage points. With the garage door closed, results will reduce by an additional 10 dB. Specific calculations are included in Attachment A at the end of this report. Rooftop equipment serving the building includes two 10-ton rooftop units, one 5-ton rooftop unit, and exhaust fans. The proposed rooftop units are manufactured by Trane and have sound power levels ranging from 82 to 86 dB(A). The exhaust fan is a downblast centrifugal 2,500 cfm fan with a sound power level of 74 dB(A). There is also a small toilet exhaust fan which produces negligible sound. The rooftop is surrounded by a tall parapet, which attenuates RTU noise. Analyses show that the total HVAC equipment sound level is well below 50 dB(A) at the nearest residences. Calculations are included at the end of this report in Attachment A. Overall, the results of this acoustical analysis indicate that the project will fully comply with all State noise code limits. HVAC equipment is shown to meet nighttime noise code limits and service bay activity during the day is shown to meet daytime noise code limits. Given the results of this analysis, no negative acoustical impact is expected from the proposed Mavis Tire Center.
Acoustical Analysis of Site Sound Emissions Proposed Mavis Tire Center #2296 - West Orange, NJ 28 June 2026 Page 4 I trust that the above is helpful. As always, if there are any questions, please let me know. Regards, OSTERGAARD ACOUSTICAL ASSOCIATES Benjamin C. Mueller, P.E., Principal bmueller@acousticalconsultant.com JCM:bcm
Acoustical Analysis of Site Sound Emissions Proposed Mavis Tire Center #2296 - West Orange, NJ 28 June 2026 Page 5 ATTACHMENT A: ACOUSTICAL CALCULATIONS Octave Band Center Frequency, Hz A† HVAC Equipment Analysis 63 125 250 500 1000 2000 4000 8000 Rooftop unit, Trane T/YSK060 5-ton, Outdoor Lw‡ 84 84 82 80 77 73 69 67 82 Attenuation due to distance, 170 feet, plus Lw to Lp§ -43 -43 -43 -43 -43 -43 -43 -43 Attenuation of rooftop parapet -5 -5 -5 -5 -5 -5 -5 -5 Total 5-ton rooftop unit Lp at residential façade 36 36 34 32 29 25 21 19 34 Rooftop unit, Trane T/YSK120 10-ton, Outdoor Lw 86 87 87 83 81 77 73 67 86 Attenuation due to distance, 138 feet, plus Lw to Lp -41 -41 -41 -41 -41 -41 -41 -41 Attenuation of rooftop parapet -5 -5 -5 -5 -5 -5 -5 -5 Total 10-ton rooftop unit Lp at residential façade 40 41 41 37 35 31 27 21 40 Rooftop unit, Trane T/YSK120 10-ton, Outdoor Lw 86 87 87 83 81 77 73 67 86 Attenuation due to distance, 95 feet, plus Lw to Lp -38 -38 -38 -38 -38 -38 -38 -38 Attenuation of rooftop parapet -5 -5 -5 -5 -5 -5 -5 -5 Total 10-ton rooftop unit Lp at residential façade 43 44 44 40 38 34 30 24 43 Exhaust Fan, Flo Aire Centrifugal Downblast, Outdoor Lw 74 78 80 69 65 63 58 52 74 Attenuation due to distance, 110 feet, plus Lw to Lp -39 -39 -39 -39 -39 -39 -39 -39 Attenuation of rooftop parapet -5 -5 -5 -5 -5 -5 -5 -5 Total exhaust fan Lp at residential façade 30 34 36 25 21 19 14 8 30 Summed rooftop units + exhaust fan at Lp at residential façade 46 47 47 43 40 36 32 27 45 N.J.A.C. 7:29 Nighttime Noise Code Limits 71 61 53 48 45 42 40 38 50 Margin of compliance 25 14 6 5 5 6 8 11 5 † A denotes the A-weighted sound level. ‡ Sound power levels, Lw, are given in dB re 1 picowatt. § Sound pressure levels, Lp, are given in dB re 20 μPa.
Acoustical Analysis of Site Sound Emissions Proposed Mavis Tire Center #2296 - West Orange, NJ 28 June 2026 Page 6 Octave Band Center Frequency, Hz A** Impact Wrench Analysis (Bay Doors Open) 63 125 250 500 1000 2000 4000 8000 Impact Wrench Lp at 50 feet, bay door open 63 57 59 63 67 66 65 66 73 Attenuation from solid fence -3 -5 -6 -8 -10 -12 -14 -16 Impact Wrench at residential property line 60 52 53 55 57 54 51 50 61 N.J.A.C. 7:29 Daytime Noise Code Limits 82 74 67 63 60 57 55 53 65 Margin of compliance 22 22 14 8 3 3 4 3 4 Impact Wrench Analysis (Bay Doors Closed) Impact Wrench Lp at 50 feet, bay door closed 64 62 54 53 55 51 47 46 54 Attenuation from solid fence -3 -5 -6 -8 -10 -12 -14 -16 Total Impact Wrench at residence 61 57 48 45 45 39 33 30 49 N.J.A.C. 7:29 Daytime Noise Code Limits 82 74 67 63 60 57 55 53 65 Margin of compliance 21 17 19 18 15 18 22 23 16 ** A denotes the A-weighted sound level.
File revisions (1)
- Sep 29, 2026
49e584bf5fb8177,627 bytes