Supporting Documentation · Nov 14, 2024
04_AECOM_Environmental Report_Final
294edc1f118d9afed4a8864a2ccbcd5a5f84aa0bf548820a10a2c5f2279b4083Indexed text · page 80
Show all pagesA-=COM Method 202 CPM Filter Thermocouple Calibration Calibrator: Fred Sanguedolce Reference Thermometer: Calibration Date: Date Received/placed Serial No.: Manufacturer's Name: 01/23/2024 in Service: 2003-2015 NA Reference Thermometer: Nutech Dry Gas Meter TC: TS 181717335 80612 Calibration Date: Omega 06022200 Calibration Date: Calibration Date: Reference Barometer: Barometric Pressure (in. Hg): Apex Instrument Part No. GN8-15K _ Ambient Temperature (°F): __01/02/2024 __09113/2023 05/24/2023, TS 181729655 30.21 $6.2 Thermocouple ID Ice Bath Boiling Water {Part ID) Actual (°F) Reference (°F) | Difference (°F) Actual (°F) Reference (°F) | Difference (°F) 2727 32 32.7 -0.7 211 212.0 1.0 4044 32 32.5 -0.5 212 212.0 0.0 4042 32 32.7 -0.7 211 212.0 -1.0 4043 32 32.5 -0.5 211 212.0 -1.0 4044 32 32.5 -0.5 211 212.0 -1.0 4045 32 327 -0.7 211 212.0 -1.0 4046 32 32.7 -0.7 211 212.0 -1.0 4047 32 32.7 -0.7 211 212.0 -1.0 4048 32 32.7 -0.7 211 212.0 -1.0 4049 32 32.7 -0.7 211 212.9 -1.0 4050 32 32.5 -0.5 212 212.0 0.0 4051 32 32.5 -0.5 210 212.0 -2.0 4052 32 32.7 -0.7 211 212.0 -1.0 4557 32 32.5 -0.5 211 212.0 -1.0 4560 32 32.7 -0.7 212 212.0 0.0 4561 32 32.7 -0.7 212 211.8 0.2 4562 32 32.5 -0.5 211 212.0 -1.0 4564 32 32.5 -0.5 212 211.8 0.2 4565 32 32.7 -0.7 212 212.0 0.0 4567 32 32.7 -0.7 211 212.0 -1.0 4568 32 327 -0.7 212 212.0 0.0 4569 32 32.5 -0.5 211 212.0 -1.0 4572 32 32.5 -0.5 212 212.0 0.0 4575 32 32.7 -0.7 212 212.0 0.0 4576 32 32.7 -0.7 212 212.9 0.0 NOTES: