Town CrierWest Orange, New Jersey
← Back to search

Supporting Documentation · Apr 15, 2026

Stormwater Management Report 03302026

Preserved file SHA-256f21e274dca0e46b0f772672884e856d0c7ea7056c08892da2245c124f65038dd

Indexed text · page 79

Show all pages
Page 79

24-223 DRAINAGE DESIGN-EXISTING-2026-03-30 NOAA 24-hr D 10-Year-2050 Rainfall=6.37", P2=4.09" Prepared by Jarmel Kizel Architects & Engnrs Printed 3/30/2026 HydroCAD® 10.20-6a s/n 12607 © 2024 HydroCAD Software Solutions LLC Page 67 Summary for Subcatchment E1A: E1A DISTURBED/IMPERVIOUS Runoff = 5.45 cfs @ 12.01 hrs, Volume= 35,712 cf, Depth= 6.13" Routed to Link 8L : EXISTING DISTURBED Runoff by SCS TR-20 method, UH=SCS, Weighted-CN, Time Span= 0.00-30.00 hrs, dt= 0.50 hrs NOAA 24-hr D 10-Year-2050 Rainfall=6.37", P2=4.09" Area (sf) CN Description 69,893 98 Paved parking, HSG C 69,893 100.00% Impervious Area Tc Length Slope Velocity Capacity Description (min) (feet) (ft/ft) (ft/sec) (cfs) 0.7 100 0.0650 2.49 Sheet Flow, Parking lot Smooth surfaces n= 0.011 P2= 4.09" 1.4 339 0.0420 4.16 Shallow Concentrated Flow, Parking lot Paved Kv= 20.3 fps 2.1 439 Total

File revisions (1)