ENSURPLAN, INC. ww.Ensurplan.net w ivil Engineers & Land Surveyors C Ph: (732) 469-0400 Certificate of Authorization 24GA27997700 STORMWATER DRAINAGE REPORT 04/13/26 Minor Subdivision 15 Ridgeway Ave West Orange, NJ Design Discussion(continued) rainage areas connected directly via roof drain piping or indirectly via flow through the D impervious pavement are shown in purple, rainage areas shown in green generate runoff which will flow overland via sheet flow to the D inlet at the rear of the site, bypassing the infiltration system. Diagram of Proposed Drainage Areas 6 Mailing Address: Post Office Box 4304, Warren, NJ 07059
ENSURPLAN, INC. ww.Ensurplan.net w ivil Engineers & Land Surveyors C Ph: (732) 469-0400 Certificate of Authorization 24GA27997700 STORMWATER DRAINAGE REPORT 04/13/26 Minor Subdivision 15 Ridgeway Ave West Orange, NJ Design Discussion (continued) he below grade infiltration basin has been sized as required to restrict the volumes of the T design storms and provide the necessary reductions in rate. It is also required that the designed pond volume can drain within 72 hours via infiltration. The maximum storage for the projected 100 year storm is 3,667 cf. Time to empty: (3,667 cf max / (125.5’ x 12.75’) sf flat bottom) x 12”/ft / 0.5”/hr = 55 hrs The maximum volume within the pond 4,026 cf. Time to empty: (4,026 cf max / (125.5’ x 12.75’) sf flat bottom) x 12”/ft / 0.5”/hr = 60 hrs he infiltration rate utilized in the design analysis is 0.5”/hour which is half of the infiltration rate T measured of 1.00”/hr at the soil log situated within the infiltration bed. 7 Mailing Address: Post Office Box 4304, Warren, NJ 07059
ENSURPLAN, INC. ww.Ensurplan.net w ivil Engineers & Land Surveyors C Ph: (732) 469-0400 Certificate of Authorization 24GA27997700 STORMWATER DRAINAGE REPORT 04/13/26 Minor Subdivision 15 Ridgeway Ave West Orange, NJ Stormwater Analysis Stormwater Quantity Requirements o comply with the Major Stormwater regulations quantity control restrictions, stormwater T management measures shall be designed so that the post-construction peak runoff rates for the current and projected 2-, 10 and 100 year storm events, as defined and determined pursuant to N.J.A.C. 7:8-5.7(c) and (d), respectively, are 50, 75 and 80 percent, respectively, of the preconstruction peak runoff rates. The percentages apply only to the post-construction stormwater runoff that is attributable to the portion of the site on which the proposed development or project is to be constructed. Design Methodology/Discussion he runoff rates from the existing condition were determined. The runoff rates from the T proposed conditions were determined. A study point is modeled at the existing inlet to the rear of the site at which all runoff from the studied area is collected. A comparison to the pre construction and post construction rates along with the maximum allowed reduced rates follows. Current Intensity Storm Pre ConstructionRate Maximum Post Construction Rate 2 Year Storm 0.38 cfs 0.19 cfs 0.19 cfs 10 Year Storm 0.95 cfs 0.71 cfs 0.66 cfs 100 Year Storm 2.26 cfs 1.81 cfs 1.80 cfs 8 Mailing Address: Post
s 1.80 cfs 8 Mailing Address: Post Office Box 4304, Warren, NJ 07059
ENSURPLAN, INC. ww.Ensurplan.net w ivil Engineers & Land Surveyors C Ph: (732) 469-0400 Certificate of Authorization 24GA27997700 STORMWATER DRAINAGE REPORT 04/13/26 Minor Subdivision 15 Ridgeway Ave West Orange, NJ Design Methodology/Discussion(continued) Projected Intensity Storm Pre Construction Rate Maximum Post Construction Rate 2 Year Storm 0.57 cfs 0.29 cfs 0.26 cfs 10 Year Storm 1.31 cfs 0.98 cfs 0.90 cfs 100 Year Storm 3.17 cfs 2.54 cfs 2.33 cfs Stormwater Recharge Requirements o comply with the Major Stormwater regulations recharge requirements, stormwater T management measures shall be designed to demonstrate through hydrologic and hydraulic analysis that the increase of stormwater runoff volume from pre-construction to post-construction for the projected two-year storm, as defined and determined pursuant to N.J.A.C. 7:8- 5.7(d), is infiltrated. Design Methodology/Discussion echarge has been provided by the use of a small scale infiltration basin and has been R analyzed by utilizing the New Jersey Groundwater Recharge Spreadsheet (NJGRS) s the NJGRS cannot model infiltration from a system which is simultaneously discharging A outflow through an orifice the study area is limited to a 2” thick stone bed set below the system outlet.The BMP variable is the depth from the surface invert of the discharge orifice or 48”. The depth to the lower surface is 50” and the effective depth of the BMP is 1.6” or 0.4 voids x 2” stone depth. 9 Mailing Address: Post Office
stone depth. 9 Mailing Address: Post Office Box 4304, Warren, NJ 07059
ENSURPLAN, INC. ww.Ensurplan.net w ivil Engineers & Land Surveyors C Ph: (732) 469-0400 Certificate of Authorization 24GA27997700 STORMWATER DRAINAGE REPORT 04/13/26 Minor Subdivision 15 Ridgeway Ave West Orange, NJ Design Methodology/Discussion(continued) he NJGRS calculation sheet was used to solve for the minimum allowable infiltration footprint T and checked against the provided area. The minimum area was calculated to be 1,339 sf while the provided infiltration footprint is 1,600 sf. As shown on the following two exhibits the required recharge volume is provided. Recharge Work Sheet One 10 Mailing Address: Post Office Box 4304, Warren, NJ 07059
ENSURPLAN, INC. ww.Ensurplan.net w ivil Engineers & Land Surveyors C Ph: (732) 469-0400 Certificate of Authorization 24GA27997700 STORMWATER DRAINAGE REPORT 04/13/26 Minor Subdivision 15 Ridgeway Ave West Orange, NJ Design Methodology/Discussion(continued) Recharge Work Sheet Two 11 Mailing Address: Post Office Box 4304, Warren, NJ 07059
ENSURPLAN, INC. ww.Ensurplan.net w ivil Engineers & Land Surveyors C Ph: (732) 469-0400 Certificate of Authorization 24GA27997700 STORMWATER DRAINAGE REPORT 04/13/26 Minor Subdivision 15 Ridgeway Ave West Orange, NJ Stormwater Quality o comply with the Major Stormwater regulations water quality requirements, stormwater T management measures shall be designed to provide 80% reduction of the post-construction load of total suspended solids (TSS) in stormwater runoff generated from the water quality design storm over the net increase of motor vehicle surface. Design Methodology/Discussion lean roof runoff and runoff from lawns, walkways, patios or decks do not have to be treated for C TSS removal. herefore discussion of water quality provision on site is limited to the remaining impervious T surface comprising driveway cover. All proposed driveways on the site are specified to be constructed of a permeable pavement system. The system is rated to provide 80% TSS removal if the storage bed below the pavement can accommodate the water quality storm. onstruction details provide a non-woven geotextile fabric underlain stone bed under all C permeable pavement with a minimum depth of 12” Void storage at a 40% ratio provides an effective depth of 4.8” well in excess of the water quality storm depth of 1.25” 12 Mailing Address: Post Office Box 4304, Warren, NJ 07059
ENSURPLAN, INC. ww.Ensurplan.net w ivil Engineers & Land Surveyors C Ph: (732) 469-0400 Certificate of Authorization 24GA27997700 STORMWATER DRAINAGE REPORT 04/13/26 Minor Subdivision 15 Ridgeway Ave West Orange, NJ Infiltration Mounding Analysis he mounding of the infiltrated water below the basin bottom is modeled utilizing the Hantush T spreadsheet calculator downloaded from the NJDEP. epth for the mounding analysis is based on the maximum depth of the projected 100 year D storm or 3.44 feet. The initial calculation inputs are as follows he recharge rate, R,or the permeability rate utilized is ½ of the measured rate of 1.0”/hr T R=0.5 “/hr he basin dimensions for spread sheet entry were 65’’ x 6.5’. Because the basin shape is linear T the spread sheet is run twice with the x and y values transposed. The specific yield utilized was the default value of 0.15. The horizontal hydraulic conductivity was set equal to the design permeability rate of 0.5”/hr. The duration of the infiltration period was calculated as follows. Infiltrated Vol (0.045 af) (43,560 sf) (12”) / Footprint (1,600 sf) (0.5”/hr) = 29 hrs The initial thickness of the saturated zone utilized was the default value of 10 feet. esults indicate a zero change in mounding at a distance 23.5’ from the long axis of the pond R and a zero change in mounding at a distance 25’ from the long axis of the pond. There are no building structures with a basement within the area which would experience an increase of ground water elevation. 13 Mailing Address: Post Office Box 4304, Warren, NJ 07059