480 3Ø GROUND SIZE & COUNT CONDUIT SIZE & TYPE 75 100 3 #2 (MIN.) 1 #2/0 2" PVC SCH.40 NOTE: CONTRACTOR MUST REFER TO THE MANUFACTURER FOR FULL ELECTRICAL DETAILS, INSTALLATION MANUAL AND SHALL BE RESPONSIBLE FOR FULL INSTALLATION TO COMPLETE THE SYSTEM. GND T NEW 150.0 KVA STEP DOWN TRANSFORMER PRIM: 480 VOLTS SEC: 120/208 VOLTS 3 PARKING/ DRIVEWAY AREA BREAKER BREAKER 250 400 #2/0 125 EXISTING GAS PIPING 100 LOCATION OF EXISTING GAS METER AND PIPINGS (ELECTRICAL FEEDS SHALL CIRCUMNAVIGATE AROUND PIPINGS AND OTHERS) PENETRATE 2" CONDUIT THROUGH WALL Project Title: 24 3 28 EXISTING SPARE 3 30 3 32 20 SPACE 34 EXISTING SPARE 35 36 3 EXISTING PANEL WITH 36 POLES HAS 1000 AMP MLO. ALL HVAC EQUIPMENT AND MOTOR LOADS SHALL HAVE HACR TYPE CIRCUIT BREAKERS EST. EXISTING LOAD: NEW LOAD: EST. TOTAL LOAD: 120.0 KVA 125.0 KVA 245.0 KVA WP J ROUTE FEEDERS TO DISCONNECT SWITCHES THROUGH THE TOP AND BOTTOM WIREWAYS ROUTE (1) 2" PVC-SCH.40 BELOW GRADE TO CHARGERS INSTALL (UG) UNDERGROUND ENCLOSURE DRIVEWAY ROUTE 2" PVC-SCH.40 BELOW GRADE TO CHARGER #1 www. bryanelectricco.com NJ Lic. # 6222 26 20 EXISTING SPARE 31 WEATHER TIGHT CONDUIT PENETRATION 22 EXISTING SPARE 29 33 20 70 30 16 18 EXISTING SPARE 25 6 14 3 3 4 12 70 70 2 10 3 3 CKT 8 EXISTING LOAD (KITCHEN) 23 27 (PRIMARY VOL: 208 VOLTS SECONDARY:480 VOLTS EXISTING LOAD (ELEVATOR) 19 21 125.0 100 3 17 (2) 480 VOLTS 100 AMP CIRCUIT BREAKER TYPE DISCONNECT SWITCH IN NEMA 1 ENCLOSURE (MIN.18 KAIC) #400KCML EXISTING LOAD ('1A') 13 15 LOCATION / ITEM EXISTING LOAD ('2A') 11 ROUTE 2" CONDUIT ALONG WALL. (ENTIRE LENGTH FROM TRANSFORMER TO THROUGH SHOULD NOT BE MORE THAN 25'-0) KVA 3 3 7 WIRE 150.0 KVA TRANSFORMER EXISTING LOAD (HVAC-2) 5 9 GND ELECTRICAL SERVICE TO EV CHARGING STATIONS WIRE E-1 KVA EV CHARGER POWER PLAN, EQUIPMENT SCHEDULE & KEY PLAN LOCATION / ITEM 1 ROUTE 4" CONDUIT ON WALL UTILITY ROOM CKT DRIVEWAY ROUTE 2" PVC-SCH.40 BELOW GRADE TO CHARGER #2 MAGNETIC INSTALL (2) CHARGE POINT EXPRESS 250 LEVEL III CHARGING STATIONS ON CONCRETE PAD (TYP OF 2) 12/23/2024 3 120 / 208 VOLT 3Ø, 4 WIRE EXISTING MAIN DISTRIBUTION PANEL 'MDP-1' Date: 400 SECTIONED MAIN DISTRIBUTION PANEL 'MDP-1' Drawing Title: CONNECT NEW FEEDER TO EXISTING 400 AMP CIRCUIT BREAKER IN PANEL EXISTING 120/208 VOLTS 1000 AMPS

Page 105

AIN DISTRIBUTION PANEL 'MDP-1' Date: 400 SECTIONED MAIN DISTRIBUTION PANEL 'MDP-1' Drawing Title: CONNECT NEW FEEDER TO EXISTING 400 AMP CIRCUIT BREAKER IN PANEL EXISTING 120/208 VOLTS 1000 AMPS SWITCHBOARD WITH SECTIONED MAIN DISTRIBUTION PANEL 'MDP-1' Drawing No: M AA 62.50 CONDUCTOR SIZE & COUNT - (1) CCS1 VEHICLE CONNECTOR, (1) CHADEMO VEHICLE CONNECTOR BREAKER Studio Park 1800 East State St., Suite 150C Hamilton, NJ 08609 609-393-8325 Bryan Electric Co. Inc. CHARGE POINT: CPE-250 EXPRESS 250 LEVEL III AMPS Drawn by: CHARGE POINT VOLTS PHASE App by: KW OLD WEST ORANGE LIBRARY AT 66 MAIN STREET W.ORANGE, NJ 08104 FEATURES AS SHOWN MANUFACTURER & EQUIPMENT Scale: MANUFACTURER EV CHARGING STATION FOR CHARGER SCHEDULE MT. PL EAS ANT AVE . EV PARKING SLOT #1 EXISTING PARKING SLOT EV PARKING SLOT #2 EXISTING PARKING SLOT EXISTING PARKING SLOT EXISTING PARKING SLOT EXISTING PARKING SLOT EXISTING PARKING SLOT EXISTING PARKING KEY PLAN 2 E-1 NO SCALE EV CHARGER POWER PLAN 1 E-1 SCALE: 1/4" = 1'-0 FOR REVIEW ONLY, NOT FOR CONSTRUCTION 12.20.2024 Phone: (856) 374-0056 Fax: (856) 374-1011 MAI AREA OF WORK 107 Coles Rd. Blackwood, NJ 08012 OLD WEST ORANGE LIBRARY WALTER W. SPENCER JR. CONSULTING ENGINEERS INSTALL (2) BOLLARDS 3'-0 ON CENTER PER CHARGER (SEE BOLLARD DETAIL) NS ROUTE (1)3" & (1)3 4" PVC-SCH.40 BELOW GRADE FOR SHARED POWER AND COMMUNICATION T. INSTALL EV CHARGER SIGN (TYP OF 2)

File revisions (1)