EXISTING 120/208 VOLTS 1000 AMPS SWITCHBOARD WITH SECTIONED MAIN DISTRIBUTION PANEL 'MDP-1' WEATHER TIGHT CONDUIT PENETRATION 480 VOLTSD 100 AMP CIRCUIT BREAKER TYPE DISCONNECT SWITCH IN NEMA 1 ENCLOSURE (MIN. 18 KAIC) U-CHANNEL SIGN POST J NEW 150.0 KVA STEP DOWN TRANSFORMER PRIM: 120/208 VOLTS SEC: 277/480 VOLTS ELEC RM. 25'-0 MAX. BOTTOM WIREWAY WEATHER PROOFED JUNCTION BOX OR CONDULET AMPS ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND INTENDED TO SHOW GENERAL POWER LAYOUTS. 4. CONTRACTOR SHALL CALL (800) 272-1000 (NJ ONE CALL) FOR MARK-OUT OF ALL UNDERGROUND UTILITIES AND SERVICES PRIOR TO COMMENCING ANY OUTDOOR WORK. 4.81 %* %Z TOLERANCE 10 % CALCULATED LET THRU CURRENT 4,168 AMPS 5. ALL ELECTRICAL WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE LATEST EDITION OF THE NEW JERSEY UNIFORM CONSTRUCTION CODE AND ALL APPLICABLE SECTIONS OF THE 2020 NATIONAL ELECTRICAL CODE. MINIMUM AIC RATING: 22,000 AMPS 6. ADJUSTMENT FACTORS FOR MORE THAN 3 CURRENT CARRYING CONDUCTORS IN A CONDUIT AND OTHERS SHALL BE APPLIED AS PER NATIONAL ELECTRICAL CODE #310.15(B). 7. ROUTING OF CONDUITS SHOWN IS FOR DESIGN PURPOSES ONLY. CONTRACTOR SHALL DETERMINE FINAL ROUTING IN FIELD. 8. ALL UNDERGROUND CONDUITS INSTALLATION MUST MAINTAIN MINIMUM 2'-0. PATCH, REPAIR & RESTORE CONCRETE/ASPHALT PAVEMENT, YARD AND OTHERS UPON COMPLETION OF WORK. 9. CHARGERS AND OTHERS SHOWN ON DRAWINGS ARE ESTIMATED LOCATIONS ONLY, PRIOR TO INSTALLATION, CONTRACTORS MUST VERIFY FIELD CONDITION AND FINAL LOCATION PRIOR TO INSTALLATION. * (Z =TRANSFORMER IMPEDANCE) PARKING AREA 6 #1 THWN 1 #8 GROUND 2" CONDUIT 2'-0 MIN. 6 #1 THWN 1 #8 GROUND 2" PVC-SCH.40 CONDUIT INSTALL (UG) UNDERGROUND ENCLOSURE 3. 3 #2 THWN 1 #8 GROUND 2" PVC-SCH.40 CONDUIT (1) CAT- 5E CABLE 3 4" PVC-SCH.40 CONDUIT CONCRETE PAD/FOOTING BELOW CHARGER (TYP PER PEDESTAL) 4 #4/0 XHHW-2 3" PVC-SCH.40 CONDUIT FOR POWER SHARING 10. CONTRACTOR SHALL MAKE ALL NECESSARY ARRANGEMENTS TO MAINTAIN THE BUILDING ELECTRICAL SERVICE AT ALL TIMES. PERIODS OF ELECTRICAL SHUT DOWN SHALL BE COORDINATED WITH OWNER AT LEAST 48 HOURS IN ADVANCE. 11. GROUNDING SHALL BE PROVIDED IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, THE UTILITY COMPANY, AND ALL AUTHORITIES HAVING JURISDICTION. ELECTRICAL SINGLE LINE DIAGRAM 12. WIRING METHODS SHALL INCLUDE SCHEDULE 40 PVC &/OR HDPE BELOW GRADE, RIGID METAL

Page 106

ONAL ELECTRICAL CODE, THE UTILITY COMPANY, AND ALL AUTHORITIES HAVING JURISDICTION. ELECTRICAL SINGLE LINE DIAGRAM 12. WIRING METHODS SHALL INCLUDE SCHEDULE 40 PVC &/OR HDPE BELOW GRADE, RIGID METAL CONDUIT, SCHEDULE 80 PVC OUTDOORS WHERE EXPOSED, ELECTRICAL METALLIC TUBING (EMT) AND METAL-CLAD CABLE INDOORS. ALL UNDERGROUND WIRING TO MEET NEC TABLE 300.5 1 E-2 NO SCALE Date: 13. MINIMUM WIRE TYPE SHALL BE TYPE "THW" OR "THHN" #12 COPPER AND 3/4 INCH MINIMUM CONDUIT. 14. VOLTAGE DROP SHALL NOT EXCEED THAT OUTLINED IN THE NATIONAL ELECTRICAL CODE #210.19(A). www. bryanelectricco.com NJ Lic. # 6222 Bryan Electric Co. Inc. 180 %Z (AS PER NAMEPLATE LABEL) 5'-0 MIN. WP FULL LOAD AMPERES Studio Park 1800 East State St., Suite 150C Hamilton, NJ 08609 609-393-8325 3 VOLTS AA 100 3 480 OLD WEST ORANGE LIBRARY AT 66 MAIN STREET W.ORANGE, NJ 08104 100 ELECTRIC VEHICLE PARKING ONLY VOLTAGE (L-L) THE CONTRACTOR SHALL MAKE ALL NECESSARY ARRANGEMENTS TO SECURE THE ELECTRICAL PERMIT. THE OWNER SHALL PAY ALL UTILITY COMPANY CHARGES REQUIRED TO SECURE SAME. AS SHOWN 3 #1 THHN 1 #8 GROUND 2" CONDUIT 3 3Ø EV CHARGING STATION FOR 400 PHASE 2. KVA ELECTRICAL SERVICE TO EV CHARGING STATIONS 3 150 Scale: 1000 INSTALL CHARGE POINT EXPRESS 250 LEVEL III CHARGING STATION ON CONCRETE PAD INSTALL EV CHARGER SIGN ON PEDESTAL FOR EACH EV PARKING SPOT (TYP OF 2) TRANSFORMER SIZE THE WORK SHALL INCLUDE ALL LABOR, MATERIALS, AND SERVICES REQUIRED TO COMPLETE THE ELECTRICAL INSTALLATION. Project Title: M TOP WIREWAY 1. 12/23/2024 CONNECT NEW FEEDER TO EXISTING 400 AMP CIRCUIT BREAKER IN PANEL ELECTRICAL SPECIFICATIONS SHORT CIRCUIT CALCULATION: Drawn by: 3 #600 KCMIL THHN 1 #2/0 GROUND 4" CONDUIT 6 #1 THHN 1 #4 GROUND 2" CONDUIT E-2 17. ALL PENETRATIONS OF RATED WALLS AND FLOORS SHALL BE SEALED WITH U.L. APPROVED FIRE-STOPPING MATERIAL. 18. NUMBERING OF CIRCUITS ON DRAWING IS FOR CONVENIENCE ONLY AND BEARS NO RELATION TO USE OF PARTICULAR CIRCUIT BREAKERS IN PANEL BOARDS. LOADS SHALL BE BALANCED AND BREAKERS SHALL BE ARRANGED IN LOGICAL OPERATING SEQUENCE. - PANEL SCHEDULE, SHORT CIRCUIT CALCULATION, SPECIFICATION & DETAILS 16. CONTRACTOR TO FURNISH AND INSTALL PULL BOXES, HAND HOLES, JUNCTION BOXES, ETC. REQUIRED TO PROPERLY ACCESS ALL CONNECTIONS. App by: Drawing Title: Drawing No: 15. ALL PANELS AND JUNCTION POINTS SHALL BE

Page 106

ACTOR TO FURNISH AND INSTALL PULL BOXES, HAND HOLES, JUNCTION BOXES, ETC. REQUIRED TO PROPERLY ACCESS ALL CONNECTIONS. App by: Drawing Title: Drawing No: 15. ALL PANELS AND JUNCTION POINTS SHALL BE PERMANENTLY LABELED. 19. ALL ELECTRICAL DEVICES SHALL BE APPROVED BY A RECOGNIZED TESTING LABORATORY AND SHALL BEAR LABEL OF THE SAME. 20. CONTRACTOR MUST FOLLOW MANUFACTURER'S INSTALLATION PROCEDURE AND PROVIDE NECESSARY COMPONENTS TO COMPLETE THE ENTIRE CHARGING STATION SYSTEM. 21. FURNISH ROUGH WIRING AND FINAL ACCEPTANCE CERTIFICATE FROM AUTHORITY PERFORMING ELECTRICAL INSPECTION. 12" 24"-0" MINIMUM* DIMENSIONS: CPE-250 2 E-2 NO SCALE FOOTING / PAD DETAILS: CPE-250 3 E-2 NO SCALE ELECTRICAL CONDUITS NOTE: 1. MARKING TAPE SHALL BE INSTALLED WHERE CONDUIT IS INSTALLED WITH OPEN TRENCH. FILL BOLLARD WITH CONCRETE & ROUND OFF AT TOP. 2. 4" SCHEDULE 40 GALVANIZED STEEL PIPE, 6'-0 LONG, PAINTED 'TRAFFIC YELLOW' MARKING TAPE SHALL NOT BE INSTALLED WHERE CONDUIT IS INSTALLED WITH HORIZONTAL DIRECTIONAL DRILL DETECTABLE UNDERGROUND MARKING TAPE, C.H. HANSEN #16635, RED, 6" WIDE, STATING "CAUTION BURIED ELECTRICAL LINE BELOW". 3'-0" EXISTING PAVING 3'-0" 15"(MIN.) TOTALLY ENCASE BOLLARD IN CONCRETE @3000 PSI * 24" MINIMUM FOR OPEN TRENCH UNDER ROADWAY. 18" MINIMUM FOR OPEN TRENCH NOT UNDER ROADWAY UNDERGROUND FEEDER DETAILS 5 E-2 NO SCALE BOLLARD DETAILS 6 E-2 NO SCALE EV CHARGER PARKING SIGN 7 E-2 NO SCALE Phone: (856) 374-0056 Fax: (856) 374-1011 GRADE OPEN TRENCH 107 Coles Rd. Blackwood, NJ 08012 CONDUIT TEMPLATE: CPE-250 4 E-2 NO SCALE WALTER W. SPENCER JR. CONSULTING ENGINEERS 22. CONTRACTOR SHALL REMOVE CONSTRUCTION DEBRIS FROM PREMISES AT THE END OF EACH DAY. UPON COMPLETION OF THE THE WORK, CONTRACTOR SHALL BROOM CLEAN AREA OF CONSTRUCTION. ALL DAMAGED SURFACES INCLUDING DRIVEWAY, SIDEWALKS, AND OTHER PAVEMENTS SHALL BE REPAIRED, AND REFINISHED AT THE END OF CONSTRUCTION PERIOD.

File revisions (1)